REYAQ-P

-VRV III Heat Recovery into water system-

Heat Recovery     
Temperaturi functionare:
-5°C ÷ +43°C
-20°C ÷ +15.5°C
Model Number Approximate Capacity [kW]
REYAQ10P8 28.0
31.5
REYAQ12P9 33.5
37.5
REYAQ14P8 40.0
45.0
REYAQ16P8 45.0
50.0
No multi combinations possible!

-Design notes-

Restrictions

- at least one Water heating unit HXHD125A must be connected in the system
- minimum 50% connection ratio must be made out of standard VRV® Indoor Units
- connection ratio range of standard VRV® Indoor Units is 50~130%
- total connection ratio range allowed is 80~200%
- technical cooling (cooling operation below -5°C outdoor temperature) not possible
- no Proportional Power Distribution of Water heating unit possible
- no centralized control via Daikin centralized controller of Water heating unit possible

-BS Boxes-

BSVQ100,160,250P9B
Branch Selector Box with single port = for one cool/heat group of up to 6 to 8 indoor units
BSV4Q100PV
Branch Selector Box with 4 ports = for four cool/heat groups of up to 6 indoor units each
BSV6Q100PV
Branch Selector Box with 6 ports = for four cool/heat groups of up to 6 indoor units each